Welcome to PDF Electric and Supply Company troubleshooting series: Troubleshooting the GE Series 90-70 PLC System.
PDF Supply has a large inventory of GE 90-70 parts, and we’ve created this article to assist users with troubleshooting techniques.
The first step to understanding the GE Series 90-70 PLC status is to inspect the LED’s on the front of the power supply and CPU. When the green power LED on the power supply is on, it indicates that all power in and out of the power supply appears to be functional.
Note: The Series 90-70 has 7 different power supply modules. See all the modules here
Power Supply Pictured IC697PWR713
If this LED is off, first check the fuse inside the power supply door. If your fuse is good, then most likely you will need to replace the power supply.
If the power supply is good, then move to the CPU located next to the power supply. A green ‘OK’ LED on the CPU means it has passed its power-up test. If this LED is not on, then replace your CPU and/or memory card mounted on the side of the CPU because there is most likely a hardware failure.
Note: The Series 90-70 has 21 CPU modules. See all the modules here
A green ‘RUN’ LED indicates that the CPU is in run mode and is solving program logic properly. Your problem could be with field devices or the I/O Enable switch inside the CPU door. It could possibly be in the improper position. If this LED is off, we will describe a troubleshooting procedure later in this video.
Finally the green ‘ENABLE’ LED should be on, which indicates that there are no faults in your CPU, and the I/O Enable switch is in the correct position inside the CPU door. Your processor is fully functional, and other non-CPU issues could be at fault.
A fourth LED remains off unless the key switch is in the ‘MEMORY PROTECT’ mode. This LED exists only with the latest series of the 90-70 CPU’s.
If you have a dead battery, your CPU may go into ‘STOP’ mode on a power cycle because you have no program.
The most common failure of the Series 90-70 PLC is the ‘RUN’ LED is off, which generally indicates that an incident has put the CPU in ‘STOP’ mode. Connect your programming unit to the RS-485 Serial Port on the PLC CPU, and then navigate to the fault tables in your programming software.
There are two basic fault tables; I/O and CPU. There you will find time and date stamp faults that have caused your system to leave ‘RUN’ mode. In many cases, it will identify rack and slot positions of the failed module. Once you have fixed the issues creating the fault, clear the fault tables so that any additional faults will be logged at the next power-up. Continue this process until your GE Series 90-70 PLC System is back up and running.
We hope our troubleshooting guide has helped you track down the problem in your PLC system.
Should you to need to repair or replace any parts for your GE Fanuc 90-70 PLC, please contact us at 1-800-360-6802 or visit our website at www.pdfsupply.com
We offer:
Tags: ge 90-70 series, GE Fanuc 90-70 PLC, ge-series 90-70 troubleshoot, IC697PWR713, trouble shooting ge fanuc plc
This entry was posted on March 27th, 2014 and is filed under GE Fanuc, Troubleshooting. Both comments and pings are currently closed.
PDF Supply sells used surplus products. PDF Supply is not an authorized distributor, affiliate, or representative for the brands we carry. Products sold by PDF Supply come with PDF Supply’s 1-year, 2-year, or 3-year warranty and do not come with the original manufacturer’s warranty. Designated trademarks, brand names and brands appearing herein are the property of their respective owners. This website is not sanctioned or approved by any manufacturer or tradename listed.
Rockwell Disclaimer: The product is used surplus. PDF Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because PDF Supply is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, PDF Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. PDF Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. PDF Supply also makes no representations as to your right to install any such firmware on the product. PDF Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.