All product names, trademarks, brands and logos used on this site are the property of their respective owners. PDF Supply is not an authorized distributor, reseller or representative of the products featured on this website. The depiction, description or sale of products featuring these names, trademarks, brands and logos is for identification purposes only and is not intended to indicate any affiliation with or authorization by any rights holder.

Product Description


The IC697MDL940 is a rugged 16-point output relay module  from the GE Fanuc 90-70  Series that scores highly on both versatility and ease of use. It operates between low and medium power loads such as lamps, contactors, and relays. The module has a rating of 2 Amps per point at a voltage of 120/240 VAC or 24 VDC. It has a current of 0.2 Amps per point for a voltage of 125VDC. The IC697MDL940 module supplies power to energize the relay coils. Each output is fused individually and suppressed with an RC snubber. Be sure to locate the LED indicators at the top of the module. Their role is to indicate the ON-OFF status of each point on the PLC module. For accurate placement with a similar PLC module, the module is mechanically keyed. Its configuration is done using MS-DOS or Windows programming software riding on a platform such as Windows 95 or Windows NT. This is usually done via over the ethernet connection using the TCP/IP protocol. The programming device can range from a personal PC, IBM XT, AT to a PS/2.

For protection, each output is fitted with a 3 Amp fuse which can be replaced with either a fast acting 3AG – 3.0 Amp with a 250 V rating. A 3 Amp 250-volt Metric 5x20mm is also perfectly suitable. The purpose of suppressing each output is to minimize the high frequency noise on the board. Moreover, suppression of the switched load is advised for improved system reliability, lengthening contact life and minimize noise at the control wiring. Each module comes with a mechanical arm for fool proof fitting. This prevents unintentional substitution or swapping of one type of module with another. The field wiring detachable board accepts wire sizes ranging from AWG#22 (0.36mm2) to AWG #14 (2.1mm2). Two wires can be terminated on a single bundle, provided they are of the same size. For this module, there’s plenty of room for routing a bundle of forty #14 wired through the board cavity. The bundle is secured onto the terminal board by a cable tie found at the terminal board’s lower corner.

For best practices during field wiring, ensure you first turn off the power before removal or installation of terminal boards. The jackscrew that secures the terminal board can be accessed upon opening the hinged door. To remove the terminal board from the module, turn the jackscrew in a counter clockwise direction until is it detached. Afterwards, grab the top of the terminal board and thereafter, swing it outwards. The terminal board can accommodate wire sizes ranging from AWG #22 (0.36mm) to AWG #14 (2.10 mm). It’s crucial to note that a maximum insulation diameter of .135 inch should not be exceeded when using AWG #14 (2.10mm) wires. For a perfect connection, two wires can be terminated on any one terminal provided they are of the same size. The design of the terminal board is such that it can only accommodate a maximum of 40 AWG #14 (2.10mm2) wires. To provide ample space for the hinged door to close, they should be placed not less than 8 inches from the end of the termination.

After all connections are completed, the wire bundles are firmly secured by cable ties. A door label is inserted to include wiring information on each module. The terminal board is designed to accept wire sizes from AWG #22 (0.36 mm) through AWG #14 (2.10 mm). It is important that when using AWG #14 (2.10 mm2) wire for wiring all points, that a maximum insulation diameter of .135 inch (3.43mm) not be exceeded. To ensure proper connection, two wires may be terminated on any one terminal only if both wires are the same size. 4. The terminal board is designed to accept a maximum of (40) AWG #14 (2.10 mm2) wires. If AWG #14 (2.10 mm2) wires are to be used, then wire markers should be placed at least 8 inches (203 mm) from termination end to provide sufficient space for the hinged door to close. 6-inch clearance above and below the rack grill is recommended to allow air-flow.

Technical Specifications


Rated Voltage: 120/240 VAC or 5/24/125 VDC
Number of Outputs:  16 (8 - Form C and 8 Form A)
Max Load Current: 16 amps per module, 4 amps per group(Form A)
Current Required: 750 mA
Freq:  47-63 Hz (AC only)
DC Power: Yes

 

16 point Relay Output, Signal, 2 Amp (16) IC697M IC697MD IC697MDL
ST. LOUIS, Feb. 1, 2019 – Emerson today announced it has completed the purchase of Intelligent Platforms from General Electric.

Common related search terms: DatasheetEmersonManualPDFPLCPriceRepairSpecificationTroubleshootUser-ManualWiring

PDF Supply sells used surplus products. PDF Supply is not an authorized distributor, affiliate, or representative for the brands we carry. Products sold by PDF Supply come with PDF Supply’s 1-year, 2-year, or 3-year warranty and do not come with the original manufacturer’s warranty. Designated trademarks, brand names and brands appearing herein are the property of their respective owners. This website is not sanctioned or approved by any manufacturer or tradename listed.

Rockwell Disclaimer: The product is used surplus. PDF Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because PDF Supply is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, PDF Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. PDF Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. PDF Supply also makes no representations as to your right to install any such firmware on the product. PDF Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.