All product names, trademarks, brands and logos used on this site are the property of their respective owners. PDF Supply is not an authorized distributor, reseller or representative of the products featured on this website. The depiction, description or sale of products featuring these names, trademarks, brands and logos is for identification purposes only and is not intended to in indicate any affiliation with or authorization by any rights holder.
PDF Supply is NOT an authorized distributor for this manufacturer and therefore the manufacturer’s warranty does not apply. Product comes with PDF Supply's 1-year, 2-year, or 3-year warranty.
Other Available Revisions for the IC693MDL940 IC693MDL940AIC693MDL940BIC693MDL940CIC693MDL940-CAIC693MDL940DIC693MDL940EIC693MDL940FIC693MDL940GIC693MDL940HIC693MDL940JIC693MDL940KIC693MDL940LIC693MDL940-LTIC693MDL940MIC693MDL940NIC693MDL940-RR
Manufacturer | Allen-Bradley / Rockwell Automation |
---|---|
Series | Series 90-30 |
Part Number | IC693MDL940 |
Product Type | Relay output module |
Voltage | 120/240 Volts AC |
Relay | 2 Amps |
Temperature | 0-60 degrees Celsius |
Isolation | 1500 Volts |
Maximum Load | 4 Amps maximum |
On/Off Response | 15 milliseconds |
Initial Power Consumption | 7 milliamps |
Enclosure | Open |
The GE Fanuc IC693MDL940 is a relay output module. Uses of this module are to control load devices like indicators, solenoids and motor starters. This module requires a switching capacity of 2A and requires a 24V DC power supply. The power supply is located on its backplane and supplies power to the module through the bus. When the IC693MDL940 involves suppression circuits, the contact life of the relay approaches the contact life of the resistive loads while switching into inductive loads. The DC and AC loads use different circuits from each other. The DC load uses the suppression circuit containing 200V diode of 1A current capacity. The suppression circuit of the AC load uses the standard components which are capacitors and resistors.
The IC693MDL940 operates in the voltage range of 5V to 30V DC supply. At the frequency range of 50Hz to 60Hz, it operates in the voltage range of 5V to 250V. Also, the module uses 16 output points in four groups containing four output points in each group. This module encounters the maximum load of 2A per output and 4A per common. The minimum load encountered is 10mA. The top of the module IC693MDL940 hosts a LED indicator which indicates the status of output points. The inside surface of the module provides the wiring information of the circuit. Either of the DC or AC power supply operate the field devices. This module does not use the fuses. The response time for switching on/off is 15msec. In 90-30 series PLC system, the user can also use the IC693MDL940 in any of the slots of the baseplate.
Rated Voltage: | 24 volts DC or 120/240 volts AC |
# of Outputs: | 16 |
Freq: | 50/60 Hz with AC |
Output Current: | 2 Amps per circuit, 4 amps per common |
Output Voltage Range: | 5 to 30 volts DC, 5 to 250 volts AC |
DC Power: | Yes |
The IC693MDL940 module is an GE Fanuc manufactured relay output module. It is a 16-point output module variant with a voltage rating of 120/240 Volts AC. It is a Series 90-30 module that is used for controlling output loads. It has an output switching capacity of 2 Amps of relay current. There are 4 groups of 4 output points each. Each of these 4 groups has a common power output terminal. This industrial relay unit controls a wide variety of load devices including solenoids, indicators, and motor starters. The IC693MDL940 module is able to handle 15 bits of output data from the host controller CPU. It can be configured BY using the Proficy Machine Edition configuration software. The relay circuit is powered through the backplane with a 24 Volts DC source.
The IC693MDL940 module is compact in size and it has a small footprint. This output module has an open enclosure and should be used for indoor applications only. The maximum operating temperature should not exceed 60 degrees Celsius for regular operation. The IC693MDL940 module comes with 1500 Volts of isolation between the field side and the logic side, and 500 Volts of isolation between groups. The relay output module can take a maximum load of 4 Amps maximum current per common. The minimum total load current is 10 Amps and the maximum inrush current is 5 Amps. The on and off response time of the module is 15 milliseconds. The initial power consumption rating of the module is 7 milliamps with 5 Volts DC voltage from the bus on the backplane, and it is 135 milliamps with 24 Volts DC voltage from the bus on the backplane.
Rated Voltage |
24 volts DC, 120/240 VAC (nominal - see the following table for exceptions) |
Operating Voltage |
5 to 30 volts DC 5 to 250 VAC, 50/60 Hz |
Outputs per Module |
16 (four groups of four outputs each) |
Isolation: |
|
Field to Backplane and to Frame Ground |
250 VAC continuous; 1500 VAC for 1 minute |
Point to Point |
250 VAC continuous; 1500 VAC for 1 minute |
Maximum Load |
2 Amps pilot duty maximum per output 4 Amps maximum per common 16 amps maximum per module |
Minimum Load |
10mA |
Maximum Inrush |
5 Amps |
On Response Time |
15ms maximum1 |
Off Response Time |
15ms maximum1 |
Power Consumption, all outputs on |
7mA from 5 volt bus on backplane 135mA from relay 24V bus on backplane |
1 When this module is used with DC power supply IC695PSD040 or PSD140, special precautions should be taken because dropouts in the source voltage will be seen by this module and may cause relay dropouts. |
Troubleshooting IC693MDL940
Troubleshooting information is available on IC693MDL940’s website page; it also includes a datasheet user-manual and a wiring diagram.
Repair your IC693MDL940
PDF Supply can repair your IC693MDL940 in 3-5 business days. And PDF Supply stands by all of its repairs with a 1 year customer satisfaction warranty.
IC693MDL940 with External Power Source for Controlling Output Loads
Description
The 2 Amp Relay Output module IC693MDL940 for the Series 90-30 Programmable Logic Controller provides 16 normally-open relay circuits for controlling output loads provided by the user.
Resolution
The output switching capacity of each output is 2 amps. The output points are arranged in four groups of four points each. Each group has a common power output terminal. The relay outputs can control a wide range of user-supplied load devices, such as: motor starters, solenoids, and indicators. Power for the internal relay circuits is provided by the +24 volt DC bus on the backplane. The user must supply the AC or DC power to operate field devices. There are no fuses on this module.
For more information on the IC693MDL940 Relay Output Module of the GE 90-30 Series, please see the Datasheet Manual.
Version |
Date |
Description |
IC693MDL940N |
May 2015 |
Change in fab color from Green to Blue. No change in form-fit-functionality. |
IC694MDL940E |
Jan 2015 |
Updated modules are RoHS converted product with applicable exemptions. |
IC693MDL940M / IC694MDL940D |
Jun 2013 |
Hardware update to resolve component obsolescence issue. No changes to features, functions or compatibility. |
IC693MDL940J / IC694MDL940A |
Aug 2008 |
Initial release. |
PDFsupply Tech
The IC693MDL940 is a 2 Amp Relay Output module for the series 90-30 Programmable Logic Controller and has 16 outputs per module, much higher than the 8 isolated outputs per module of the IC693MDL930. The user must supply the power to operate field devices.
Common related search terms: BuyDatasheet, Emerson, Manual, Price, Repair, Specification, Troubleshoot, Wiring,
PDF Supply sells used surplus products. PDF Supply is not an authorized distributor, affiliate, or representative for the brands we carry. Products sold by PDF Supply come with PDF Supply’s 1-year, 2-year, or 3-year warranty and do not come with the original manufacturer’s warranty. Designated trademarks, brand names and brands appearing herein are the property of their respective owners. This website is not sanctioned or approved by any manufacturer or tradename listed.
Rockwell Disclaimer: The product is used surplus. PDF Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because PDF Supply is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, PDF Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. PDF Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. PDF Supply also makes no representations as to your right to install any such firmware on the product. PDF Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.