GE / IP FANUC Series 90/30 In Stock

World's Largest Warehouse

of GE 90-30, Genius, and RX7i

Mon-Fri 8AM-5PM EST

IC695EDS001

RX3i EDS001 Accessory

Rated 4.5/5 Based on 2 ratings.

Rate your purchase of the IC695EDS001
GE IP Ethernet DNP3 Slave/Outstation Module Rx3i PACSystems DNP3 Ethernet Outstation | Image

SKU 2173304  UPC 0799705806764

All product names, trademarks, brands and logos used on this site are the property of their respective owners. PDF Supply is not an authorized distributor, reseller or representative of the products featured on this website. The depiction, description or sale of products featuring these names, trademarks, brands and logos is for identification purposes only and is not intended to in indicate any affiliation with or authorization by any rights holder.

PDF Supply is NOT an authorized distributor for this manufacturer and therefore the manufacturer’s warranty does not apply. Product comes with PDF Supply's 1-year, 2-year, or 3-year warranty.

New

$3946

3 In Stock

✓  2 Year PDF Supply Warranty

*Need a Specific Revision?

Ships .

New Surplus

$2985

Save $961

1 In Stock

✓  3 Year PDF Supply Warranty

*What is New Surplus?

Ships .

Common misspellings:
  • 1C695EDS001
  • IC695EDSo01
  • IC695EDS0o1
  • IC695EDS00l
  • IC695EDS001

Product Description


The IC695EDS001 is a DNP3 Slave/Outstation Module from the GE Fanuc RX3i Series.  This module connects an RX3i controller to a DNP3 network using a standard Ethernet TCP/IP connection scheme.  See specifications for this unit on IC695EDS001's website page.

 

Technical Information

Specifications

 

Module Name

PACSystems RX3i DNP3 Outstation Module

Catalog

IC695EDS001

Protocol Supported

DNP3 Outstation

CPU Compatibility

CPU320/CPU315, CPU310/CMU310/NIU001,

CRU320/CRU320QP, CPE310 firmware version 6.0 or later

Programmer Compatibility

Proficy Machine Edition 8.5 SIM7 or later

Connectors

Station Manager (RS-232) Port: 9-pin female D-connector

Two 10BaseT / 100BaseTX Ports: 8-pin female shielded RJ-45

LAN

IEEE 802.2 Logical Link Control Class I

IEEE 802.3 CSMA/CD Medium Access Control 10/100 Mbps

Number of IP addresses

One

Number of Ethernet Port Connectors

Two: both 10BaseT / 100BaseTX with auto-sensing RJ-45 connection.

Embedded Ethernet Switch

Yes Allows daisy chaining of Ethernet nodes. Ring networks not permitted.

Serial Port

Station Manager Port: RS-232 DCE, 1200 - 115200 bps.

Modules per RX3i CPU

4 (max - depends on power and slots available)

No. of DNP3 Masters supported per module

8 per module (max)

No. of DNP3 Masters supported per RX3i CPU

32 per RX3i CPU (max)

No. of DNP3 points per

module

12,072

No. of DNP3 events per module

20,000

Network Topology supported

Star, Line, Daisy Chain

RX3i Slot Location

Any I/O Slot in Main Rack.

Hot Swappable

Yes. Refer to  Chapter  2  of  PACSystems RX3i System Manual, GFK-2314E or later for instructions & restrictions.

Time Synchronization

SNTP Client, DNP3 Time  Synchronization

Power Requirements

3.3Vdc: 840 mA maximum

5Vdc: 614 mA maximum

Troubleshooting

Troubleshooting IC695EDS001

Troubleshooting information is available on IC695EDS001's website page; it also includes a datasheet user-manual and a wiring diagram.


Repair your IC695EDS001

PDF Supply can repair your IC695EDS001 in 3-5 business days. And PDF Supply stands by all of its repairs with a 1 year customer satisfaction warranty.

Customer Questions and Answers


  • Question:  What is an IC695EDS001?  Answer:  IC695EDS001 is a DNP3 Slave/Outstation Module from the GE Fanuc RX3i Series.
  • Question:  What does IC695EDS001 do for the RX3i system?   Answer:  This module connects an RX3i controller to a DNP3 network using a standard Ethernet TCP/IP connection scheme.
  • Question:  How does the IC695EDS001 operate?  Answer:  This module allows a DNP3 Master to poll data from the Slave Station, and can set up the Master to receive unsolicited communications from the Slave.
  • Question:  What are some of the operating features?  Answer:  
    • Up to 4 EDS001 per RX3i, as allowed by available power and slots
    • Supports insertion into and removal from an RX3i backplane under power
    • Data exchanges up to 12,072 points and 20,000 events supported
    • Firmware upgrades using WinLoader software utility
    • Supports unsolicitated data communications with DNP3 Master
  • Question:  Where must IC695EDS001 be located?  Answer:  IC695EDS001 can be installed in any available RX3i main rack I/O slot.
  • Question:  What should I do if my IC695EDS001 is not working properly?  Answer:  Your IC695EDS001 may need repair.

For more information on the IC695EDS001 DNP3 Slave/Outstation Module of the GE Fanuc RX3i Series, please see the Datasheet User-Manual.

Release History

 

Catalog Number

Firmware Version

 

Date

 

Comments

IC695EDS001-CE

Firmware 6.40 /1.40

Feb 2016

An enhancement was made to prevent the module from becoming

unresponsive and requiring a power cycle if it was subjected to heavy network storm traffic.

IC695EDS001-CD

Firmware 6.31 /1.30

 

Boot 3.71

Dec 2015

This hardware release addresses an issue identified, where the module can unexpectedly go into firmware update mode (Ethernet OK, LAN OK, and Log Empty LEDs blink in unison). While in firmware update mode, the module is unresponsive to Ethernet traffic. There are no changes to form, fit, or function.

 

This Firmware provides enhancements to configure the Event Buffer size separately for Digital Inputs (BI – Binary Inputs and BO – Binary Output status) and Analog Inputs ( AI – Analog Inputs and AOS – Analog Output status) and  also support specific DNP3 object variations. This also fixes issue with module

going unexpectedly in firmware update mode, as part of the Web upgrade kit.

IC695EDS001-BC

1.20

Jul 2015

This firmware release fixes the issue related to IIN Bits indicating Class1 and   Clas2 Data Available status to DNP3 Master. The firmware also corrects the  control code for Close and Trip Control (Close=101) and (Trip =110) in the CROB

Control DWORD to be consistent with description in User manual –Section 6.9.2.

IC695EDS001-BB

1.10

Apr 2015

Added a feature to support different control codes like PULSE ON/OFF, CLOSE, TRIP and LATCH ON/OFF for the CROB Control objects. This also enhanced the Quality functionality for ensuring that events are generated when quality is offline, and appropriate quality status is updated.

This hardware release addresses a component obsolescence issue. There are

no changes to form, fit, or function.

IC695EDS001-AA

1.00

Oct 2014

Initial release.

 

ST. LOUIS, Feb. 1, 2019 – Emerson today announced it has completed the purchase of Intelligent Platforms from General Electric.

PDF Supply sells used surplus products. PDF Supply is not an authorized distributor, affiliate, or representative for the brands we carry. Products sold by PDF Supply come with PDF Supply’s 1-year, 2-year, or 3-year warranty and do not come with the original manufacturer’s warranty. Designated trademarks, brand names and brands appearing herein are the property of their respective owners. This website is not sanctioned or approved by any manufacturer or tradename listed.

Rockwell Disclaimer: The product is used surplus. PDF Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because PDF Supply is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, PDF Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. PDF Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. PDF Supply also makes no representations as to your right to install any such firmware on the product. PDF Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.