All product names, trademarks, brands and logos used on this site are the property of their respective owners. PDF Supply is not an authorized distributor, reseller or representative of the products featured on this website. The depiction, description or sale of products featuring these names, trademarks, brands and logos is for identification purposes only and is not intended to in indicate any affiliation with or authorization by any rights holder.
PDF Supply is NOT an authorized distributor for this manufacturer and therefore the manufacturer’s warranty does not apply. Product comes with PDF Supply's 1-year, 2-year, or 3-year warranty.
Other Available Revisions for the IC695PSA040 IC695PSA040AIC695PSA040EIC695PSA040FIC695PSA040GIC695PSA040HIC695PSA040JIC695PSA040KIC695PSA040-LT
Manufacturer | GE Fanuc |
---|---|
Series | RX3i PACSystems |
Part Number | IC695PSA040 |
Product Type | Power Supply Module |
Voltage Type | AC and DC |
AC Voltage Range | 85 to 264 Volts AC |
DC Voltage Range | 100 to 300 Volts DC |
Input Power at a Full Load | 70 Watts |
Backplane Isolation | 250 Volts AC Continuous, and 1500 Volts AC for 1 Minute |
Backplane | RX3i Universal Backplane |
The IC695PSA040 is a 120/240 volt AC or 125 volt DC, 40 Watt Power Supply from the GE Fanuc RX3i Series. It can work with an input source of either alternating or direct current. Its operating voltage is 85-264 VAC or else 100-300 VDC.
The RX3i power supply has three outputs:
+3.3 VDC - for internal use by RX3i modules that have IC695 catalog numbers.
+5.1 VDC
+24 VDC relay - can be used to power circuits on Output Relay modules.
The PACSystems RX3i power supply is a scalable, rack-based system, which provides fast and consistent control between separate modules. Users can develop and maintain their own custom control functions. This includes visualisation, motion, and networking.
Another great feature is the PACMotion Controller that provides all the flexibility and machine logic necessary to use advanced machine automation in your business.
Though designed specifically to support the PACSystem RX3i, only one IC695PSA040 power supply can be installed in the Universal Backplane at a time. The power supply is not compatible with other RX3i supplies, either in increased capacity or redundant modes.
The power supply has four LEDs that indicate the power supply’s status. The power LED is the top one and will be green when power is supplied to the backplane or amber if the power supply switch is off. When the P/S Fault LED glows red, the supply has failed and is not supplying voltage to the backplane. When the power supply is close to the maximum operating temperature or is above it, the Overtemp LED glows amber. When the power supply is close to or over the maximum output capability on any output, the Overload LED glows amber.
It is important that the door of this unit remains closed during operation. This prevents against shock hazards, which could cause severe or fatal injuries.
Rated Voltage: | 120/240 VAC or 125 VDC |
Input Voltage Range: | 85 to 264 VAC or 100 to 300 VDC |
Number of Slots: | 2 |
Output Power: | 40 Watts max |
Output Voltage: | 24 VDC, 5.1 VDC or 3.3 VDC |
Output Current: | 0-1.6 A, 0-6 A, or 0-9 Amps |
The IC695PSA040 module is an industrial power supply module from the GE Fanuc RX3i PACSystems series that is made to supply the power to devices in the RX3i PACSystems PLCs. The IC695PSA040 power supply module can provide devices with AC voltage in the range of 85 to 264 Volts AC, and with DC voltage in the range of 100 to 300 Volts DC. Its maximum input power rating at a full load is 70 Watts. The nominal input voltage ratings of the IC695PSA040 power supply module are 120/240 Volts AC and 125 Volts DC. It supports isolation between the input and the backplane that is rated at 250 Volts AC continuously and at 1500 Volts AC for 1 minute.
The GE Fanuc IC695PSA040 RX3i PACSystems power supply module has 3 different outputs. The first output is the 3.3 Volts DC rated output that is meant for connecting to other RX3i PACSystems modules that are part of the RX3i IC695 product line. The second output is rated at 5.1 Volts DC, and the third output is rated at 24 Volts DC and it is meant to power the circuits on compatible output relay modules. The IC695PSA040 power supply module should never be installed on any backplane that is not an RX3i PACSystems universal backplane, and only 1 IC695PSA040 power supply module can be used at a time in an RX3i PACSystems PLC. This power supply cannot be used in any kind of redundancy system. This power supply module is scalable and it comes with machine logic.
Nominal Rated Voltage Input Voltage Range AC DC |
120/240 VAC or 125 VDC
85 to 264 VAC 100 to 300 VDC |
Input Power (Maximum with Full Load) |
70 Watts maximum |
Inrush Current |
4 Amps, 250 milliseconds maximum * |
Output Power |
40 Watts maximum total 5.1 VDC = 30 Watts maximum 3.3 VDC = 30 Watts maximum The maximum total output power available depends on the surrounding air temperature, as shown. |
Output Voltage |
24 VDC: 19.2 VDC to 28.8 VDC 5.1 VDC: 5.0 VDC to 5.2 VDC (5.1 VDC nominal) 3.3 VDC: 3.1 VDC to 3.5 VDC (3.3 VDC nominal) |
Output Current |
24 VDC: 0 to 1.6 Amps 5.1 VDC: 0 to 6 Amps 3.3 VDC: 0 to 9 Amps |
Isolation (input to backplane): |
250 VAC continuous; 1500 VAC for 1 minute |
Ripple (all outputs) |
150 mV |
Noise (all outputs) |
150 mV |
Ride-through time |
20 ms. This is the length of time the Power Supply maintains valid outputs if the power source is interrupted |
Wiring Terminals |
Each terminal accepts one 14 AWG to 22 AWG wire. |
Current per Terminal |
6 Amps |
Number of Daisy-Chained PSA040 Supplies |
Up to 4 |
Troubleshooting IC695PSA040
Troubleshooting information is available on IC695PSA040's website page; it also includes a datasheet user-manual and a wiring diagram.
Repair your IC695PSA040
PDF Supply can repair your IC695PSA040 in 3-5 business days. And PDF Supply stands by all of its repairs with a 1 year customer satisfaction warranty.
For more information on the IC695PSA040 120/240 VAC or 125 VDC, 40 Watt Power Supply of the GE Fanuc RX3i Series, please see the Datasheet User-Manual.
Version |
Date |
Details |
IC695PSA040J |
May 2013 |
Increases the margin of the 5V and 3.3V under voltage detectors to prevent PS faults during power-up. |
IC695PSA040H |
Aug. 2012 |
Resolves an issue with powering up under light loads. |
IC695PSA040G |
Jun. 2011 |
Hardware modification improves radiated RF susceptibility and removes the requirement to install control systems that use this product in a grounded metal enclosure to meet the EU EMC Directive. |
IC695PSA040F |
Sep. 2006 |
Hardware modification. Previous versions of this Power Supply occasionally failed to power up when installed in a 16-Slot Universal Backplane, IC695CHS016. This update resolves the issue. |
IC695PSA040E |
Mar. 2006 |
The D version of this Power Supply (IC695PSA040D) incorrectly reported that it was a PSA140 power supply, causing a Configuration Mismatch error. The E version and versions prior to D report their identification correctly. |
IC695PSA040A |
Oct. 2005 |
Initial release |
Common related search terms: BatteryBuy, Configuration, Datasheet, Dimension, Emerson, Fanuc, Firmware, GE-Fanuc, Manual, PDF, PLC, Price, Repair, Specification, Troubleshoot, User-Manual, Wiring,
PDF Supply sells used surplus products. PDF Supply is not an authorized distributor, affiliate, or representative for the brands we carry. Products sold by PDF Supply come with PDF Supply’s 1-year, 2-year, or 3-year warranty and do not come with the original manufacturer’s warranty. Designated trademarks, brand names and brands appearing herein are the property of their respective owners. This website is not sanctioned or approved by any manufacturer or tradename listed.
Rockwell Disclaimer: The product is used surplus. PDF Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because PDF Supply is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, PDF Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. PDF Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. PDF Supply also makes no representations as to your right to install any such firmware on the product. PDF Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.